Method for Estimating Ultraviolet Germicidal Fluence Rates in a Hospital Room

  • Millie P. Schafer (a1), Elmira Kujundzic (a2), Clyde E. Moss (a3) and Shelly L. Miller (a2)

Abstract

Background.

Upper-room air UV germicidal irradiation (UVGI) is an effective environmental control measure for mitigating the transmission of airborne infections. Many factors influence the efficacy of an upper-room air UVGI system, including the levels and distribution of radiation. The radiation levels experienced by airborne microorganisms can be estimated by measuring the fluence rate, which is the irradiance from all angles that is incident on a small region of space.

Methods.

The fluence rate can be estimated by use of a radiometer coupled to a planar detector. Measurements in 4 directions at a single point are taken and summed to estimate the fluence rate at that point. This measurement process is repeated at different sites in the room at a single height.

Results.

In the upper air of a test room, the UV fluence rate varied at least 3-fold, with the maximum rate occurring in the immediate vicinity of the fixtures containing lamps emitting UV radiation. In the area that would be occupied by the patient and/or healthcare personnel, no significant variation occurred in the UV fluence rate for a designated height. There was no significant statistical difference between measurements obtained by different individuals, by using a different alignment, or during 5 observation periods. Lamp failures were detected on multiple occasions.

Conclusion.

This method is simple, requires no specialized training, and permits regular monitoring of the necessary UV fluence rates needed to sustain the targeted airborne microorganisms' inactivation level. Additionally, this method allowed for the detection of changes in UV fluence rates in the upper air of the simulated hospital room.

Copyright

Corresponding author

US Department of Health and Human Services, Public Health Service, Centers for Disease Control and Prevention, National Institute for Occupational Safety and Health, 4676 Columbia Parkway, MS R-7, Cincinnati, OH 45226-1099 (mps3@cdc.gov)

References

Hide All
1.Pearson, ML, Jereb, JA, Frieden, TR, et al.A nosocomial transmission of multidrug-resistant Mycobacterium tuberculosis: a risk to patients and health care workers. Ann Intern Med 1992;117:151156.
2.Beck-Sagué, C, Dooley, SW, Hutton, MD, et al.Hospital outbreak of multidrug-resistant Mycobacterium tuberculosis infections in a hospital: factors in transmission to staff with HIV-infected patients. JAMA 1992;268:12801286.
3.Valway, SE, Greifinger, RB, Papania, M, et al.Multi-drug resistant tuberculosis in the New York State Prison System, 1990-1991. J Infect Dis 1994;170:151156.
4.Cooper-Arnold, K, Morse, T, Hodgson, M, et al.Occupational tuberculosis among deputy sheriffs in Connecticut. Appl Occup Environ Hyg 1999;14:768776.
5. DHHS (NIOSH) publication no. 94-106. In: Bierbaum, PJ, Lippmann, M, eds. Proceedings of the Workshop on Engineering Controls for Preventing Airborne Infections in Workers in Health Care and Related Facilities. Washington, DC: US Government Printing Oiffice; 1994:552578.
6.Centers for Disease Control and Prevention. National action plan to combat multidrug-resistant tuberculosis: meeting the challenge of multidrug-resistant tuberculosis: summary of a conference; management of persons exposed to multi-drug-resistant tuberculosis. MMWR Recomm Rep 1992;41(RR-11):148.
7.Brickner, PW, Vincent, RL, First, M, Nardell, E, Murray, M, Kaufman, W. The application of ultraviolet germicidal irradiation to control transmission of airborne disease: bioterrorism countermeasure. Public Health Rep 2003;118:99114.
8.Well, WF. Radian disinfection of air. Arch Phys Therapy 1942;23:143148.
9.Riley, RL, Knight, M, Middlebrook, G. Ultraviolet susceptibility of BCG and virulent tubercle bacilli. Am Rev Respir Dis 1976;113:413418.
10.Riley, RL, O'Grady, F. Viability, infectivity, and virulence of airborne organisms. In: Riley, RL, O'Grady, F, eds. Airborne Infection: Transmission and Control. New York: MacMillan; 1961:5880.
11. Hanovia. Glossary. Available at: http://www.hanovia.com/information/glossary.aspx. Accessed June, 11 2008.
12.Moes, CJM, van Gemert, MJC, Star, WM, Marijnissen, JPA, Prahl, SA. Measurements and calculations of the energy fluence rate in a scattering and absorbing phantom at 633 nm. Appi Opt 1989;28:22922296.
13.Xu, P, Kujundzic, E, Peccia, J, et al.Impact of environmental factors on efficacy of upper-room air ultraviolet germicidal irradiation for inactivating airborne mycobacteria. Environ Sci Technol 2005;39:96569662.
14.Dumyahn, T, First, M. Characterization of ultraviolet upper room air disinfection devices. Am Ind Hyg Assoc J 1999;60:219227.
15.Xu, P, Peccia, J, Fabian, P, et al.Efficacy of ultraviolet germicidal irradiation of upper-room air in inactivating airborne bacterial spores and mycobacteria in full-scale studies. Atmos Environ 2003;37:405419.
16. Prolight. UV Disinfection-application information. Available at: http://prolight.info/pdf_specs/Philips_UV_tech_brochure.pdf. Accessed July 29, 2007.
17.Black, DR, Harley, RA, Hering, SV, Stolzenburg, MR. A new, portable, realtime ozone monitor. Environ Sci Technol 2000;34:30313040.
18.International Light Technologies. Detector: SEL (SED) 240. Available at: http://intl-lighttech.com/products/detectors/detectordata/se240. Accessed July 29, 2007.
19.International Light Technologies. Standard calibration services. Available at: http://www.intl-lighttech.com/calibrations/standard-calibration-services. Accessed June 10, 2008.
20.Hogg, RV, Tanis, EA. Probability and Statistical Inference. 4th ed. New York: MacMillan; 1993.
21.Björn, LO. Estimation of fluence rate from irradiance measurements with a cosine corrected sensor. J Photochem Photobio B Biol 1995;29:179183.
22.Rahn, RO, Xu, P, Miller, SL. Dosimetry of room-air germicidal (254 nm) radiation using spherical actinometry. Photochem Photobiol 1999;70:314318.
23.Kujundzic, E, Miller, SL, Hernandez, M. Ultraviolet germicidal irradiation inactivation of airborne fungal spores and bacteria in upper-room air and HVAC in-duct configurations. J Env Eng Sci 2007;6:19.
24.American Conference of Governmental Industrial Hygienists (ACGIH). Threshold limit values for chemical substances and physical agents and biological exposure indices. Cincinnati, Ohio: ACGIH; 2004.
25.National Institute for Occupational Safety and Health (NIOSH). NIOSH criteria documents. Criteria for a recommended standard: occupational exposure to ultraviolet radiation. DHHS (NIOSH) publication no. HSM 73-11009;1972. Available at: http://www.cdc.gov/niosh/73-11009.html. Accessed September 15, 2008.
26.First, MW, Weker, RA, Yasui, S, Nardell, EA. Monitoring human exposures to upper-room germicidal ultraviolet irradiation. J Occup Environ Hyg 2005;2:285292.
Recommend this journal

Email your librarian or administrator to recommend adding this journal to your organisation's collection.

Infection Control & Hospital Epidemiology
  • ISSN: 0899-823X
  • EISSN: 1559-6834
  • URL: /core/journals/infection-control-and-hospital-epidemiology
Please enter your name
Please enter a valid email address
Who would you like to send this to? *
×

Metrics

Altmetric attention score

Full text views

Total number of HTML views: 0
Total number of PDF views: 0 *
Loading metrics...

Abstract views

Total abstract views: 0 *
Loading metrics...

* Views captured on Cambridge Core between <date>. This data will be updated every 24 hours.

Usage data cannot currently be displayed